Е-YY-J, Е-YY-O
A power cable suitable for use in air, soil, concrete, enclosed locations, cable ducts, power plants, industrial applications, city power grids – where mechanical damages are not expected, and cables are not exposed to excessive pulling forces. HD 603 S1:1994/A3:2007, IEC60332-1-2.
SPECIFICATIONS
Short-circuit temperature:
Temperature limits | -30 °C to +70 °C |
Max. temperature of a conductor | +70 °C |
Short-circuit temperature: | |
• for cross-section area ≤300mm2 | +160 °C |
• for cross-section area >300mm2 | +140 °C |
Bending radius: | |
• single-core cables | 15 x overall diameter |
• multi-core cables | 12 x overall diameter |
Colors available: Black.
Core Identification:
Е-YY -J:
- 1 cond.: Green/Yellow;
- 3 cond.: Green/Yellow – Brown – Blue;
- 4 cond.: Green/Yellow – Grey – Black – Brown;
- 5 cond.: Green/Yellow – Grey – Black – Brown – Blue.
Е-YY-O:
- 1 cond.: Black;
- 2 cond.: Brown, Blue;
- 3 cond.: Brown, Black, Grey;
- 4 cond.: Blue, Brown, Black, Grey;
- 5 cond.: Blue, Brown, Black, Grey, Black.