APPLICATION:
Halogen-free
N2XH cables with improved fire properties can be installed under or over
concrete, in wet or dry locations, cable channels, open air, but it is not
intended for direct burial or under the water. It is recommended for
public buildings (hotels, hospitals, department stores, subways, theatres,
cinemas etc.) and in all other public buildings where good flame
properties in case of fire are required to prevent developing poisonous
gases and corrosive HCL gases. During installation cables have to be protected
from any external influences or mechanical damages.
PACKING:
Available on drums.
Photos of our products:
CONSTRUCTION:Number of cores: 1 to 5
Conductor cross-section: 1.5 to 1000 mm2
1 - Conductor: Cu – class 1 and 2
2 - Insulation: Cross-linked PE, XLPE, type 2XI1
3 - Core: HFFR halogen-free polymer compound
4 - Jacket: HFFR polymer compound type HM4
SPECIFICATION:Type N2XH
Standard DIN VDE 0276
Nominal voltage 0.6/1 kV
Test voltage 4000 V
Minimum temperature during installation -5°C
Operating temperature -30°C - +90°C
Maximum operating temperature +90°C
Short circuit temperature +250°C/5s
Flame-retardant test IEC 60332-3
Minimum bending radius 12x d of cable
Coat colour Black