APPLICATION:
High temperature, flame retardant cable used in
switchgear, controlgear and instrumentation panels, and for purpose such as
internal connectors in rectifier equipment, motor starters and controllers.
PACKING:
Available in sealed coils or on drums.
CONSTRUCTION:Number of cores: 1
Conductor cross-section: 0.5 to 240 mm
2
1 – Class 5 flexible copper conductor, plain
annealed, according to BS EN 60228
2 – Insulation – heat resistant PVC Type TI3
according to BS EN 50363
Installation conditions
Minimum installation temperature: 5°C
• Recommended minimum bending radius: 6 times the
cable diameter
• Recommended maximum tensile stress: 50 N/mm² of the
cross-section of the copper
SPECIFICATION:
Type: Tri-rated - H05V2-K / H07V2-K / BS 6231 UL1015
CSA 22.2 Flexible PVC Cable
Standards: BS EN
50525-2-31* BS 6231 Type CK, UL Subj.758, CSA C22.2 No. 210 (HD 21.7 S2)
#LL246095, BS EN/IEC 60332;
TRI-RATED - UL -
CSA – BS (0,5 ÷ 240 mm²); BI-RATED - UL – CSA (300 ÷ 500 mm²); H07V2-K - EN (1,5 ÷ 35 mm²)
Voltage rating: UL, CSA:
450/750V
BS 6231: 600/1000V
BS EN 50525-2-31: 300/500V, 450/750V450/750 V
Test voltage 2500 V
Operating temperature -40°C - +90°C
Maximum operating temperature +105°C
Short circuit temperature +160°C
Thermal endurance properties (temperature index TI):
110°C referring to 20.000 hours (BS EN 60216-1)
Flame-retardant test IEC 60332-1
Minimum bending radius 6 x d of cable